Zelio Logic smart relay
Environmental characteristics
Approvals UL, CSA, C-TICK, GL
Degree of protection
IP 20
Temperature Operation °C - 20...+ 55 conforming to IEC 68-2-1 and 68-2-2
Readability of display °C 0...+ 55 conforming to IEC 68-2-1 and 68-2-2
Storage °C - 25...+ 70 (conforming to IEC 1131-2)
Maximum relative humidity
% 95 without condensation or dripping water
Altitude
m 0…2000
Mechanical resistance Immunity to vibrations Conforming to standard IEC 68-2-6, test Fc
Immunity to mechanical shock Conforming to standard IEC 68-2-27, test Ea
Resistance to electrostatic discharge
Immunity to electrostatic discharge Conforming to standard IEC 61000-4-2, level 3 (1)
Resistance to HF interference
Immunity to electromagnetic Conforming to standard IEC 61000-4-3, level 3 (1)
radiated fields
Immunity to rapid Conforming to standard IEC 61000-4-4, level 3 (1)
pulsed transients
Immunity to surges Conforming to standard IEC 61000-4-5
Immunity to damped Conforming to standard IEC 61000-4-12
oscillatory waves
Connection to screw terminals Flexible cable with cable end mm
2
1 conductor : 0.141.5, cable : AWG26AWG16
(Tightened using Ø 3.5 screwdriver)
2 conductors : 0.140.75, cable : AWG26AWG18
Semi-rigid cable mm
2
1 conductor : 0.142.5, cable : AWG26AWG14
Rigid cable mm
2
1 conductor : 0.142.5, cable : AWG26AWG14
2 conductors : 0.141.5, cable : AWG26AWG16
Tightening torque N.m 0.6
Supply characteristics $
Smart relay type SR1- B121JD A101BD
B121BD
A201BD
B201BD
B122BD
Primary
Nominal voltage V 12 24
Voltage limits
Including ripple V 10.4...14.4 19.230
Nominal input current
mA 105 83 130 45
Heat dissipation
W 1.3 1.6 2.9 1.1
Micro-breaks
Acceptable duration 1 ms, repeated 20 times
Protection
Against polarity inversion
Supply characteristics "
Smart relay type SR1- B101B B201B A101FU
B101FU
A201FU
B201FU
Primary
Nominal voltage V 24 100...240
Voltage limits
Including ripple V 20.426.4 85...264
Nominal frequency
Hz 50-60 (4763)
Nominal input current
mA 80 130 100 V 50
240 V 27
100 V 80
240 V 40
Heat dissipation
W 3 5 3 5.3
Micro-breaks
Acceptable duration 10 ms, repeated 20 times
Isolation voltage
Primary/earth V 2000 (50-60 Hz)
Processing characteristics
Smart relay type SR1- A1 , B1 A2 , B2
Number of control scheme lines 60 80
Maximum cycle time
ms 6 8
Response time (2)
ms 12 to 24 (SR1-B121JD and
1 BD)
14 to 26 (SR1- 201BD)
20 to 40 (SR1- 101FU and
101B)
22 to 42 (SR1- 201FU and
201B)
Back-up time in case of power failure
Day/time h 150 at 40 °C only applicable to SR1-B and SR1-E (4)
Programme and adjustments For life, internal EEPROM
Current values and states (3) For life, internal EEPROM on smart relays SR1B/SR1E only (4)
Programme memory checking
At each power-up
Clock drift
s 6 per month
Time delay block accuracy
± 12 ms ± 0.5 % of the time displayed
(1) Minimum level under test conditions defined by the standards.
(2) Time between change of state of an input and change of state of an output directly linked by the programme in the same cycle
(3) The values and states to be saved must be configured in the remanence menu.
(4) As from product version V1.7.
Characteristics